Replaceable Core Filter-Drier

ref. Replaceable Core Filter-Drier

Filter-drier shells with replaceable cores are designed for big system protection. The large capacity models are ideal for new system startups to remove moisture and solid particle contamination from field piping. The replaceable core design also simplifies continued system protection and preventive maintenance initiatives. Replacing cores routinely ensures lowest possible moisture levels and clean oil.



Air conditioning Commercial Refrigeration Heat Pump

General Characteristics

Aftermarket ModelSolder Connection ODFNumber of cores
(sold separately)
Capacity (tons) 1
  (inch)   R-134a R-404A R-22 R-407C2 R-410A
FDSH-48-5-S 5/8 1 18,6 13,1 19,2 19,2 19,2
FDSH-48-7-S 5/8 18,6 13,1 19,2 19,2 19,2
FDSH-48-9-S 7/8 29,8 20,9 30,8 30,8 30,8
FDSH-48-11-S 1 3/ 8 42,8 30,1 44,2 44,2 44,2
FDSH-96-7-S 7/8 2 112 78,5 115 115 115
FDSH-96-9-S 1 1/ 8 18,6 13,1 19,2 19,2 19,2
FDSH-96-11-S 1 3/8 29,8 20,9 30,8 30,8 30,8
FDSH-96-13-S 1 5/8 42,8 30,1 44,2 44,2 44,2
FDSH-144-9-S 1 1/8 3 101 70,6 104 104 104
FDSH-144-11-S 1 3/8 112 78,5 115 115 115
FDSH-192-11-S 1 3/8 4 70,8 49,7 73 73 73
FDSH-192-13-S 1 5/8 101 70,6 104 104 104
FDSH-192-17-S 2 1/8 112 78,5 115 115 115
               
  CORE MODELS            
Aftermarket Model Description Filter Media          
FD Core 48 
All Purpose Core Filter-Drier Core 80% desiccant          
FD Core 48 
Hi Moisture Core Filter-Drier Core 100% desiccant          

Features

  • System protector for optimum performance and efficiency
  • Effective and efficient: filters solid particles, adsorbs moisture and removes acid
  • Large filtering area removes solid particles contamination to an extremely low level of 20 microns
  • FD Core 48 All Purpose
    Applicable refrigerant: R22, R134a, R404A, R407C and R507
    Applicable hybrid refrigerant: R124, R125, R134a, R143a, R152a, R218, R23 and R32
    Great desiccation ability is applicable under wide range of temperature showing high pressure educability and excellent anti-shock performance. The even size of desiccant beads removes impurities effectively and keep low pressure drop.
    Composition of solid element: 80 % 3A Desiccant, 20% active alumina for acid absorption.
  • FD Core 48 Hi Moisture
    Applicable refrigerant: R134a, R 404a and R 407C etc.
    Great water absorption performance, effectively filters out impurities
    100% 3A desiccant can work with POE oil with strong moisture absorption capability.

General specifications

  • Applicable refrigerant: HCFC, HFC and CFC
  • Applicable medium temperature: -50°C ~ +120°C (-58°F ~ +248°F)
  • Applicable ambient temperature: -50°C ~ +80°C (-58°F ~ +176°F)
  • Maximum working pressure: HTG-A48: PB = 35 bar, HTG-A96: PB = 35 bar, HTG-B44: PB = 35 bar, HTG-B92: PB = 28 bar
  • UL/PED