4-Way Reversing Valve

4-Way Reversing Valve

Sanhua Reversing Valves switch between cooling and heating mode by changing the flow of the refrigerant. The solder connection at the pilot tube and valve allows for increased reliability and low leakage probability. The Reversing Valves are compatible with all common HCFC and HFC refrigerants and are UL recognized with a maximum operating pressure of 650 psig.

Technical parameters

  • Features
    • Solder connection pilot tube and valve for increased reliability
    • Compatible with all common HCFC and HFC refrigerants 
    • Suitable for capacities from 1-120 tons
    • Available bi-stable coil provides energy savings
  • Specifications
    • Applicable for all common HCFC and HFC refrigerants such as: 
      R22, R134a, R404A, R407C, R410A, R507
    • Min./max. ambient temperature: -30°C (-22°F) / +50°C (122°F) or +70°C (158°F) (Depending on used coil)  
    • PS: 4,5 MPa (45 bar)
    • TS min./max.: -30°C (-22°F) / +135°C (275°F)
    • Relative humidity below 95%
    • Certifications: UL/CSA** and declaration according to LVD or PED
  • Nominal operating conditions
    Nominal operating conditions Condition 1: Condition 2:
    Condensing Temperature t_c 38°C 54°C
    Evaporating Temperature t_o 5°C 7,2°C
    SuperHeating dt_oh 5K 5K
    SubCooling dt_u 0K 5K
  • Capacity selection

    Aftermarket Model Nominal Cooling Capacity (tons - condition 2)
    R-407C R-410A R-134a R-404A/R-507
    Pressure Drop (PSI)
    1,5 3 1,5 3 1,5 3 1,5 3
    SHF(L)-4H-23U 0,91 1,31 1,08 1,54 0,74 1,05 0,74 1,05
    SHF(L)-7H-34 1,68 2,36 1,96 2,76 1,34 1,88 1,34 1,88
    SHF(L)-7H-34U 1,68 2,36 1,96 2,76 1,34 1,88 1,34 1,88
    SHF(L)-7H-35 1,68 2,36 1,96 2,76 1,34 1,88 1,34 1,88
    SHF-7H-45 1,68 2,36 1,96 2,76 1,34 1,88 1,34 1,88
    SHF-9H-45D1-L1 2,1 2,9 2,4 3,4 1,6 2,3 1,6 2,3
    SHF(L)-11H-46D1 2,59 3,67 3,04 4,29 2,08 2,93 2,08 2,93
    SHF-14-46 3,81 5,37 4,46 6,31 3,04 4,29 3,04 4,29
    SHF-14-47 3,81 5,37 4,46 6,31 3,04 4,29 3,04 4,29
    SHF-14-56D1 3,81 5,37 4,46 6,31 3,04 4,29 3,04 4,29
    SHF-20A-45 5,49 7,76 6,4 9,07 4,38 6,17 4,38 6,17
    SHF-20A-56D1 5,49 7,76 6,4 9,07 4,38 6,17 4,38 6,17
    SHF-20A-57D1 5,49 7,76 6,4 9,07 4,38 6,17 4,38 6,17
    SHF-20D-46-02 5,49 7,76 6,4 9,07 4,38 6,17 4,38 6,17
    SHF-35B-47-02 5,49 7,76 6,4 9,07 4,38 6,17 4,38 6,17
    SHF-35B-47-04 8,47 12 9,92 14 8,47 9,58 6,77 9,55

    Note:

    • Condition 2. Condensing temperature 130°F;
    • evaporating temperature +45°F;
    • Superheat and Subcooling temperature 9°F

     

  • Technical parameters
    Project / Shared Model Cooling & Heating Type
    Voltage DC12V±10%, AC24V±10%, AC100V~AC240V
    Frequency 50Hz/60Hz
    Construction mode One-unit, duel-panel FR-4 design
    Ambient temperature and humidity -20ºC ~ +70ºC, 10% ~ 95%
    Storage environment temperature and humidity -30ºC ~ +85ºC, 10% ~ 95%
    Rated Electric Input Power 20VA
    Max. Electric Input Power 30VA
    Applicable Expansion Valve Type Q series, O series, S series , R series , T series
    Applicable Expansion Valve Port Size 1.3mm ~ 6.5mm
    Applicable Expansion Valve Full Open Pulse 500Pulse, 2000Pulse
    Applicable Expansion Valve Excitation Mode 1~2 phase excitation, 2~2 phase excitation
    Size 90x70mm, 100x80mm, 110x90mm, available for customization as per customers’ needs
    Certification 3C/CE/ETL/TUV/UL(including EMC)
Download icon

Download Full Technical Information