SeriesModelPart numberActuationKv [m3/h]Max. OPD [Mpa]Min. OPD [Mpa]MOP [Mpa]Normal PositionSeat mmTube OD [inch]Tube OD [mm]
FDF2A94FDF-06001Direct0,083,404,5NC1,91/46,35
FDF2.5A06FDF-06002Pilot0,23,40,014,5NC2,51/46,35
FDF3A08FDF-06003Pilot0,263,40,014,5NC35/167,94
FDF4A10FDF-06004Pilot0,33,40,014,5NC41/46,35
FDF6A58FDF-06005Pilot0,563,40,014,5NC5,85/167,94
FDF8A21FDF-06006Pilot1,292,80,014,5NC83/89,52
FDF11A05FDF-06007Pilot2,42,80,024,5NC111/212,7
FDF13A07FDF-06008Pilot3,442,80,024,5NC135/815,88

Features

  • Coils: low energy consumption, reliable hybrid desiccant
  • Great valve opening performance, high mopd.

General specifications

  • Applicable refrigerant: R22, R134a, R407C, R410A etc.
  • Applicable medium temperature: -30ºC (-22°F) ~ +120ºC (248°F);
  • Applicable ambient temperature: -30ºC (-22°F) ~ +50ºC (122°F);
  • Relative humidity: below 95%
  • Maximum working pressure: 4.5MPa (45 Bar);
  • Certification: UL, TUV

Technical Parameters

Technical Parameters of Valve Body

ModelPart numberNormal positionActuationSeat mmKv [m3/h]MOP [MPa]Max. OPD [MPa]Min. OPD [MPa]Tube OD [mm]Tube OD [inch]
FDF2A94 FDF-06001 NC Direct 1.9 0.08 4.5 3.4 0 6.35 1/4
FDF2.5A06 FDF-06002 NC Pilot 2.5 0.2 4.5 3.4 0.01 6.35 1/4
FDF3A08 FDF-06003 NC Pilot 3 0.26 4.5 3.4 0.01 7.94 5/16
FDF4A10 FDF-06004 NC Pilot 4 0.3 4.5 3.4 0.01 6.35 1/4
FDF6A58 FDF-06005 NC Pilot 5.8 0.56 4,5 3.4 0.01 7.94 5/16
FDF8A21 FDF-06006 NC Pilot 8 1.29 4,5 2.8 0.01 9.52 3/8
FDF11A05 FDF-06007 NC Pilot 11 2.4 4,5 2.8 0.02 12.7 1/2
FDF13A07 FDF-06008 NC Pilot 13 3.44 4,5 2.8 0.02 15.88 5/8

Technical Parameters of Coil

ModelPart NumberRated Voltage [V]Power [W]Frequency HzVoltage ToleranceInsulation ClassWiring Type
FQ-A05024-000709 FQ-A55001 24 AC

10.5W(50Hz)

8.5W (60Hz)

50/60

-15%

+10%

B flying leads
FQ-A05120-000709 FQ-A55002 110 to 120 AC

10.5W(50Hz)

8.5W (60Hz)

FQ-A0522G-001044 FQ-A55003 220 to 240 AC

12W(50Hz)

10W (60Hz)

Dimensions

Solenoid Valve FDF Normally Close Series . FDF2A with FDF2A65 as the standard Product

FDF2A with FDF2A65 as the standard Product

Solenoid Valve FDF Normally Close Series . Equipped with FQ-A05 Series Coil

Equipped with FQ-A05 Series Coil

Solenoid Valve FDF Normally Close Series . FDF6A with FDF6A42 as the standard Product

FDF6A with FDF6A42 as the standard Product

Solenoid Valve FDF Normally Close Series . Equipped with FQ-A05 Series Coil

Equipped with FQ-A05 Series Coil

Solenoid Valve FDF Normally Close Series . FDF8A with FDF8A09 as the standard Product

FDF8A with FDF8A09 as the standard Product

Solenoid Valve FDF Normally Close Series . Equipped with FQ-A03 Series Coil

Equipped with FQ-A03 Series Coil

Solenoid Valve FDF Normally Close Series . FDF11A with FDF11A05 as the standard Product

FDF11A with FDF11A05 as the standard Product

Solenoid Valve FDF Normally Close Series . Equipped with FQ-A05 Series Coil

Equipped with FQ-A05 Series Coil

Solenoid Valve FDF Normally Close Series . FDF13A with FDF13A07 as the standard Product

FDF13A with FDF13A07 as the standard Product

Solenoid Valve FDF Normally Close Series . Equipped with FQ-A05 Series Coil

Equipped with FQ-A05 Series Coil