Coil for Electronic Expansion Valve series DPF T S
T/S series electronic expansion valves are designed for usage in air conditioning and refrigeration systems or in heat pumps. The valve supports automatic adjustment of refrigerant flow rate and makes the system work under optimized conditions for the purpose of fast cooling or heating, precise temperature control and energy saving. The valve can also be used e.g. for suction line pressure controls. These valves provide bidirectional operation to control the refrigerant flow rate in heating or cooling mode.
Technical parameters
-
Features
- Applicable for oil-free system (T series)
- Smaller installation space: low height, small volume, light weight
- Optimized flow path design for noise reduction
- Fast operation, Energy saving
- Applicable for reversible systems like heat pumps: bidirectional flow
-
General specifications
- Applicable refrigerants: R22, R134A, R404A, R407C, R410A etc.
- Cooling Capacity: 3,5 to 105 kW (R22 Nominal Capacity)
- Medium temperature: -30°C to +70°C (duty cycle rate below 50%)
- Ambient temperature: -30°C to +60°C (duty cycle rate below 50%)
- Relative humidity: below 95% RH
- Installation position: Coil upwards, valve rotor central axis within +/-15° versus vertical axis
- 500 steps (full stroke); 32 ± 20 opening steps
-
Electrical Parameters
- Rated Voltage: 12V DC(+/- 10%), rectangular wave
- Actuating mode: 4-phase 8-step permanent magnet stepping motor of direct-acting type
- Excitation mode: 1 ~ 2 phase excitation, monopole actuation
- Excitation rate: 30 to 90pps (Maintain excitation in stop position min. 0.1~1.0sec. to activate self-holding mechanism.)
- Coil current: 260mA/phase (20°C)
- Coil resistance: 46 +/- 3.7 ?/phase (20°C)
- Insulation class of coil: E
- Protection class: IP 66
-
General characteristics
Model Part Number Seat ? (mm) Kv (m3/h) Nominal Cooling Capacity (kW) MOP Max. Oper. Press. (MPa) MOPD Direct (MPa) MOPD Rev. (MPa) R22 R134a R407C R404A
R507R410A DPF(T01)1.3C-07 DPF-09001 1,3 0,05 3,5 2,7 3,5 2,5 4,2 4,2 3,43 ?2.1 DPF(T01)1.65C-05 DPF-09002 1,65 0,08 5,3 4,1 5,3 3,7 6,36 DPF(T01)1.8C-08 DPF-09003 1,8 0,1 7 5,4 7 4,9 8,4 DPF(T01)2.0C-03 DPF-09004 2 0,16 8,75 6,7 8,75 6,1 10,5 DPF(T01)2.2C-01 DPF-09005 2,2 0,2 10,5 8,1 10,5 7,4 12,6 DPF(T01)2.4C-01 DPF-09006 2,4 0,23 17,5 13,5 17,5 12,3 21 DPF(TS1)3.0C-01 DPF-09007 3 0,39 21 16,2 21 14,7 25,2 ?1.47 DPF(TS1)3.2C-01 DPF-09008 3,2 0,43 28 21,6 28 19,6 33,6 DPF(S03)4.0C-01 DPF-09010 4 0,5 42 32,3 42 29,4 50,4 ?0.7 DPF(S03)4.5C-01 DPF-09011 4,5 0,7 52,5 40,4 52,5 36,8 63 DPF(S03)5.5C-01 DPF-09012 5,5 0,9 70 53,9 70 49,0 84 3 DPF(S03)6.5C-02 DPF-09013 6,5 1,1 105 80,9 105 73,5 126 (*) Nominal working conditions: Condensing temperature: 38°C; evaporating temperature 5°C; Sub cooling 0K; Superheating 0K
-
Flow characteristic
-
Dimensions
Valve Model Coil Series Dimensions (mm) Part No. A B C D E DPF(T01)1.3C-07
to
DPF(TS1)3.2C-01PQ-M10012-000001 38,5 26,4 25,6 700 600 DPF-58001 DPF(S03)4.0C-01
to
DPF(S03)6.5C-02PQ-M03012-000001 67,5 42,4 33 700 600 DPF-58002
Download Full Technical Information
Need even more detail or going offline? Find here all the technical specifications and product data.
Datasheet